MWC UNIT # |
POLLUTANT OR PARAMETER |
START DATE |
TIME OF EXCESS EMISSIONS |
MONITORED LEVEL |
APPLICABLE LIMIT |
SPECIFIC REASON FOR EXCESS |
CORRECTIVE ACTIONS TAKEN |
1 |
CO |
1/26/2006 |
0800 |
1159 |
107 |
69 |
Encountered gas burner light off problems |
Had Electrical technician replace faulty equipment on fire starter to gas burners. |
1 |
CO |
2/24/2006 |
2000 |
2359 |
131 |
69 |
shutdown for planned maintenance activity |
removed MSW from grates ASAP to minimize emissions |
1 |
CO |
3/5/2006 |
1200 |
1559 |
465 |
69 |
UPS power supply to DCS computers malfunctioned shutting down operations to both units |
contacted E/I technicians who responded and reset electrical breakers, bypassed UPS and restarted computers |
1 |
CO |
3/5/2006 |
1600 |
1959 |
79 |
69 |
MSW was present on grates and relit when Combustion fans were restarted |
continued combustion process using msw present on grates. |
2 |
CO |
3/5/2006 |
1200 |
1559 |
101 |
69 |
Shutdown |
Closed up unit until communication with computers could be established |
2 |
CO |
3/5/2006 |
1600 |
1959 |
90 |
69 |
gas in service during restarting of the plant |
Gas Burners in service during startup process |
1 |
CO |
4/4/2006 |
1600 |
1959 |
116 |
69 |
shutdown for planned maintenance activity |
removed MSW from grates ASAP to minimize emissions |
2 |
CO |
5/5/2006 |
2000 |
2359 |
100 |
69 |
shutdown for planned maintenance activity |
removed MSW from grates ASAP to minimize emissions |
2 |
CO |
5/7/2006 |
1200 |
1559 |
131 |
69 |
Restarting of the plant after planned facility maintenance activity |
Gas Burners in service during startup process |
2 |
CO |
6/28/2006 |
2000 |
2359 |
90 |
69 |
shutdown for planned maintenance activity |
removed MSW from grates ASAP to minimize emissions |