SUMMARY REPORT - GASEOUS AND OPACITY EXCESS EMISSION AND MONITORING SYSTEM PERFORMANCE |
 |
COMPANY: |
Wheelabrator North Andover Inc. |
ADDRESS: |
285 HOLT ROAD |
|
NORTH ANDOVER, MASSACHUSETTS 01845 |
 |
PROCESS UNIT DESCRIPTION: |
MUNICIPAL SOLID WASTE RESOURCE RECOVERY FACILITY |
 |
POLLUTANT: |
UNIT #2 SO2 |
UNIT #2 NOx |
UNIT #2 CO |
UNIT #2 OPACITY |
REPORTING PERIOD DATES: |
10/01/08-12/31/08 |
10/01/08-12/31/08 |
10/01/08-12/31/08 |
10/01/08-12/31/08 |
EMISSION LIMITATION: |
29ppm@7%O2 |
205ppm@7%O2 |
69ppm@7%O2 |
10% |
MONITOR MFG. & PRIMARY COMPONENTS: |
Western Research Photmetric |
Thermo Environmental |
Thermo Environmental |
Land Combustion Mark 4500 ll+ |
DATE OF LATEST CEMS CERTIFICATION AUDIT: |
12/10/2008 |
12/10/2008 |
12/10/2008 |
12/10/2008 |
TOTAL SOURCE OPERATING TIME IN REPORTING PERIOD: |
2100 |
2100 |
2100 |
126000 |
EMISSION DATA SUMMARY |
DURATION OF EXCESS EMISSIONS IN REPORTING DUE TO: |
A. STARTUP/SHUTDOWN |
0 |
0 |
0 |
0 |
B. CONTROL EQUIPMENT PROBLEMS |
0 |
0 |
0 |
0 |
C. PROCESS PROBLEMS |
0 |
0 |
0 |
0 |
D. OTHER KNOWN CAUSES |
0 |
0 |
0 |
0 |
E. UNKNOWN CAUSES |
0 |
0 |
0 |
0 |
TOTAL DURATION OF EXCESS EMISSION |
0 |
0 |
0 |
0 |
TOTAL DURATION OF EXCESS EMISSION ÷ TOTAL SOURCE OPERATING TIME (X 100) |
0.0%
|
0.0%
|
0.0%
|
0.0%
|
CEMS PERFORMANCE SUMMARY |
CEMS DOWNTIME IN REPORTING PERIOD DUE TO: |
A. MONITOR EQUIPMENT MALFUNCTIONSS |
2.00 |
28.00 |
2.00 |
0 |
B. NON-MONITOR EQUIPMENT MALFUNCTIONS |
0.00 |
0.00 |
0.00 |
0 |
C. QUALITY ASSURANCE CALIBRATION |
1.00 |
1.00 |
1.00 |
88 |
D. OTHER KNOWN CAUSES |
18.00 |
18.00 |
18.00 |
37 |
E. UNKNOWN CAUSES |
0.00 |
0.00 |
0.00 |
0 |
TOTAL CEMS DOWNTIME |
21.00 |
47.00 |
21.00 |
125 |
TOTAL CEMS DOWNTIME ÷ TOTAL SOURCE OPERATING TIME (X 100) |
1.0%
|
2.2%
|
1.0%
|
0.10%
|
DESCRIBE ANY CHANGES SINCE LAST QUARTER IN CEMS, PROCESS OR CONTROLS: |
|
|
|
|
|
|