SEMI-ANNUAL REPORTING FOR CONTINUOUS MONITORING SYSTEMS AND STACK TESTING
MWC UNIT # POLLUTANT OR PARAMETER START DATE TIME OF EXCESS EMISSIONS MONITORED LEVEL APPLICABLE LIMIT SPECIFIC REASON FOR EXCESS CORRECTIVE ACTIONS TAKEN
1 CO 5/24/2004 20:00 23:59 125 69 Malfunction: utility trip, lost pumps, fans, etc. restart plant systems, light burners
1 OPACITY 5/8/2004 14:30 14:36 13 10 Opacity spiked when returning compartments to service following maintenance activities instructed employees to gradually open inlet damper when returning compartments to service
2 CO 1/2/2004 04:00 07:59 326 69 Shutdown: planned outage, average based on only 1 hour of operation followed normal shutdown procedures using gas burners
2 CO 1/4/2004 08:00 11:59 588 69 Shutdown: planned outage, average based on only 1 hour of operation followed normal shutdown procedures using gas burners
2 CO 1/15/2004 00:00 03:59 878 69 Malfunction: tube leak developed while returning boiler to operations which required shutdown, average is based on only 2 hours of operations removal of msw from feed table was required since the unit was off gas burners when leak developed
2 CO 1/23/2004 00:00 03:59 149 69 Shutdown: superheater tube leak, average based on only 1 hour of operation followed emergency shutdown procedures
2 CO 2/18/2004 08:00 11:59 2452 69 Shutdown: furnance tube leak, average based on only 1 hour of operation followed emergency shutdown procedures, unable to safely fire gas burners due to tube leak location
2 CO 3/24/2004 20:00 23:59 79 69 Shutdown: planned outage, average based on only 1 hour of operation followed normal shutdown procedures using gas burners
2 CO 3/28/2004 00:00 03:59 209 69 Startup: following maintenance activities return plant to service following scheduled facility outage
2 CO 4/19/2004 16:00 19:59 81 69 Shutdown: superheater tube leak, average based on only 1 hour of operations followed normal shutdown procedures using gas burners
2 CO 6/28/2004 12:00 15:59 100 69 Malfunction: plant air compressor system down reduced load until air system could be restarted and repressurized