SEMI-ANNUAL REPORTING FOR CONTINUOUS MONITORING SYSTEMS AND STACK TESTING
MWC
UNIT #
POLLUTANT
OR
PARAMETER
START
DATE
mm/dd/yyyy
START FINISH MONITORED
LEVEL
APPLICABLE
LIMIT
SPECIFIC REASON
FOR EXCESS
CORRECTIVE
ACTIONS TAKEN
                 
1 CO 2/7/2003 0303 0359 226 69 startup gas used
1 CO 2/19/2003 2124 2144 203 69 emergency shutdown due to tube leak followed emergency shutdown procedures
1 CO 5/19/2003 0901 0924 260 69 shutdown followed normal shutdown procedures
2 CO 1/6/2003 0939 1000 150 69 Shutdown for planned outage followed normal shutdown procedures
2 CO 1/9/2003 1431 1454 149 69 startup gas used
2 CO 1/24/2003 0215 0227 82 69 Shutdown for planned outage followed normal shutdown procedures
2 CO 3/23/2003 0824 0839 265 69 Shutdown for planned outage followed normal shutdown procedures
2 CO 4/4/2003 0443 0522 79 69 startup gas used
2 CO 5/12/2003 2115 2129 227 69 emergency shutdown due to tube leak followed emergency shutdown procedures
Wheelabrator North Andover
285 Holt Rd.
North Andover, Massachusetts, U.S. 01845
Tel: 978.688.9011

Copyright © Wheelabrator North Andover