SEMI-ANNUAL REPORTING FOR CONTINUOUS MONITORING SYSTEMS AND STACK TESTING
MWC
UNIT #
POLLUTANT
OR
PARAMETER
START
DATE
mm/dd/yyyy
START FINISH MONITORED
LEVEL
APPLICABLE
LIMIT
SPECIFIC REASON
FOR EXCESS
CORRECTIVE
ACTIONS TAKEN
                 
1 CO 1/28/2002 2000 2400 312 69 shutdown followed shutdown procedures
1 CO 2/3/2002 0800 1200 559 69 shutdown followed shutdown procedures
2 CO 3/7/2002 0000 0400 469 69 turbing tripped-malfunction of lube oil system, back up system failed ti maintain pressure switch initiated emergency response procedures to reduce steam load, secure and stablize units and plant.
1 CO 3/7/2002 0000 0400 293 69 turbing tripped-malfunction of lube oil system, back up system failed ti maintain pressure switch initiated emergency response procedures to reduce steam load, secure and stablize units and plant.
2 CO 3/20/2002 1200 1600 219 69 shutdown due to tube leak followed shutdown procedures
2 CO 3/21/2002 2000 2400 273 69 shutdown due to tube leak followed shutdown procedures
2 CO 4/19/2002 1600 2000 84 69 shutdown due to tube leak followed shutdown procedures
1 CO 4/29/2002 0400 0800 457 69 shutdown due to tube leak followed shutdown procedures
2 CO 5/12/2002 0000 0400 237 69 shutdown due to tube leak followed shutdown procedures
1 CO 5/15/2002 1200 1600 187 69 planned shutdown followed shutdown procedures
2 CO 5/17/2002 2000 2400 135 69 planned shutdown followed shutdown procedures
2 CO 5/19/2002 0800 1200 365 69 while returning facility to operation a tube leak developed which required unit to be shutdown for repairs followed shutdown procedures
1 CO 6/26/2002 1600 2000 97 69 fire at substation knocked turbine off line and analyzers initiated emergency response procedures to reduce steam load, secure and stablize units and plant.
2 CO 6/26/2002 1600 2000 537 69 fire at substation knocked turbine off line and analyzers initiated emergency response procedures to reduce steam load, secure and stablize units and plant.
2 CO 6/27/2002 0000 0400 211 69 start-up of plant delayed had to reset Turbine control limits to 2 boiler operation status